Causes of industrial chiller failure(1)

Nov 21, 2024

  1. Causes and remedies for high condensing pressure (higher than the specified value):
    ① There is non-condensable gas in the system: release the non-condensable gas.
    ② The cooling water volume of the chiller is insufficient and the water temperature is too high: check whether the water valve is open and whether the water filter is blocked, and try to lower the water temperature.
    ③ There is dirt in the condenser that affects the heat transfer area: clean the condenser.
    ④ There is too much liquid in the condenser: release the excess refrigerant.